Back

TRINITAS ACADEMY

1101 SW 49th Ave, Plantation, FL 33317

License:
C17BO0516
Type:
Child Care Facility
Status:
Licensed
Records checked:
July 11, 2026
Additional info
Programs and services:
VPK, After School, Before School, Drop In, Full Day, Half Day
Hours:
Mon-Fri: 7:00AM to 6:00PM; Sat-Sun: Closed
Capacity:
37
License expiration:
September 30, 2026
Typical cost: $1,235 - $1,387 (Under 1)
Child’s age

$1,235 - $1,387/mo

Median daily rate: $57.00 - $64.00

Official Florida Division of Early Learning Broward County data.

Not this provider’s price.

Google reviews

Ratings and reviews are from users of Google Maps, and are not related to DaycareFacts.com inspection report analysis.

See reviews on Google Maps

Inspection snapshot

Recent higher-concern violation

At least one higher-concern violation appears in the last 12 months.

Next: Read reports, examine repeated topics below, look at the broader history, and ask what changed afterward.

Latest inspectionMay 13, 2026
Latest inspection with no recorded violationsMay 13, 2026

Summary

This summary covers 19 available inspections for TRINITAS ACADEMY from April 17, 2023 through May 13, 2026.

Eight inspections recorded violations, with 11 recorded violations in total.

The most recent higher-concern violation was on April 15, 2026 and involved transportation, with a due date of April 29, 2026.

A later inspection showed no recorded violations, but the records do not say whether it was a formal follow-up.

At a glance

Total inspections
19

4 in last 12 months

Recorded violations
11

2 in last 12 months

Higher-concern violations
1

1 in last 12 months

Repeated topics
2

Last 36 months

Local comparison

19 total inspections vs 12 local median in 33317

Compared to 18 local facilities

Recorded violations per inspection

This provider
0.58
Local median
0.17

Inspections with higher-concern violations

This provider
5%
Local median
9%

Inspections with recorded violations

This provider
42%
Local median
17%

Repeated topics

This provider
2
Local average
0.72

Repeated topics

Topics that appeared in more than one inspection during the last 36 months. They may reveal a pattern worth examining.

Inspection history

Available inspection history. Select a violation topic for more info.

View official report
Medium concern: Equipment or readiness
Report finding
3.5(F), Handbook: The outdoor play area must have adequate fencing or walls a minimum of 4 feet in height. Fencing, including gates, must be continuous and must not have gaps or opening larger than 3 inches that would allow children to exit the outdoor play area. The base of the fence must remain at ground level, and be free from erosion or build-up to prevent inside and outside access by children or animals. These areas must have at least two exits, with at least one being remote from the buildings. If an outdoor play area was approved for usage by the Department prior to October 25, 2017, no new exits are required to be added to meet this standard. However, if outdoor play area fencing is changed then the standard would apply and two exits must be provided. The facilitys fencing was inadequate in that [see below].
Report comments
- The white fence surrounding the playground was missing the gate latch. Since the gate is damaged, the children have access to the basketball court area and the fence in the basketball area is in poor condition. There are broken and missing panels throughout the perimeter in the basketball courts. - The white fence facing the road has a missing metal pole, causing a gap larger than 3 and 1/2 inches. This is the fourth occurrence of this non-compliance and a Notice of Violation is being issued.
Correction status
Due by April 29, 2026
More details
Report section
PHYSICAL ENVIRONMENT - 21 - Outdoor Play Space Group: Sec. 7-37, Ordinance and DCF Handbook
Official code
21-11
Higher concern: Transportation
Report finding
3.8.4(C), Handbook: The operator must maintain a written record of the fire drills showing the date, number of children and child care personnel in attendance, evacuation route used, and time taken for all individuals to evacuate the premises. Each fire drill record must be maintained for a minimum of 12 months from the date of the fire drill. The facilitys record of fire drills was missing [documentation of feb. and march drills], or was not maintained for 12 months.
Report comments
The facilitys fire drill was missing records for the drills conducted in February and March. TA was provided on conducting monthly fire dirlls.
Correction status
Due by April 29, 2026
More details
Report section
TRANSPORTATION - 48 - Fire Drills/Emergency Procedures Group: DCF Handbook
Official code
48-02
Medium concern: Health or food records
Report finding
7.1, Handbook: The child care facility is responsible for obtaining for each child in care a current, complete and properly executed Florida Certification of Immunization form Part A-1, B, or C, DH 680, which is incorporated by reference in 65C-22.001(7)(o), F.A.C., or the Religious Exemption from Immunization form, DH 681, which is incorporated by reference in 65C-22.001(7)(p), F.A.C., from the custodial parent or legal guardian. The Florida Certificate of immunization was expired for children in care.
Report comments
This standard was cited on previous inspection report dated 4/10/2025. During today's visit it remains non-compliant since 3 of 7 children continue to have expired shot records on file.
Correction status
Due by June 3, 2025
More details
Report section
HEALTH REQUIREMENTS - 37 - Health Examinations/Health Maintenance Group: Sec. 7-43, Ordinance and DCF Handbook
Official code
37-04
View official report
Medium concern: Equipment or readiness
Report finding
3.5(F), Handbook: The outdoor play area must have adequate fencing or walls a minimum of 4 feet in height. Fencing, including gates, must be continuous and must not have gaps or opening larger than 3 inches that would allow children to exit the outdoor play area. The base of the fence must remain at ground level, and be free from erosion or build-up to prevent inside and outside access by children or animals. These areas must have at least two exits, with at least one being remote from the buildings. If an outdoor play area was approved for usage by the Department prior to October 25, 2017, no new exits are required to be added to meet this standard. However, if outdoor play area fencing is changed then the standard would apply and two exits must be provided. The facilitys fencing was inadequate in that [the fence panels are broken, missing].
Report comments
The necessary repairs from previous revisit inspection were completed. During today's routine inspection, the white fence surrounding the play area was missing or had loose slabs and exposed screws. Places where slabs were missing, allow access to an area that has lots of clutter including, wires, machinery, metal or plastic panels leaning against the walls. This is the third occurrence of this non-compliance and notice of violation is being issued.
Correction status
Due by April 24, 2025
More details
Report section
PHYSICAL ENVIRONMENT - 21 - Outdoor Play Space Group: Sec. 7-37, Ordinance and DCF Handbook
Official code
21-11
Medium concern: Health or food records
Report finding
7.1, Handbook: The child care facility is responsible for obtaining for each child in care a current, complete and properly executed Florida Certification of Immunization form Part A-1, B, or C, DH 680, which is incorporated by reference in 65C-22.001(7)(o), F.A.C., or the Religious Exemption from Immunization form, DH 681, which is incorporated by reference in 65C-22.001(7)(p), F.A.C., from the custodial parent or legal guardian. The Florida Certificate of immunization was expired for children in care.
Report comments
Children files were checked and all files had either missing or expired shot records. See supplemental for details.
Correction status
Due by May 2, 2025
More details
Report section
HEALTH REQUIREMENTS - 37 - Health Examinations/Health Maintenance Group: Sec. 7-43, Ordinance and DCF Handbook
Official code
37-04
View official report
Medium concern: Equipment or readiness
Report finding
3.5(F), Handbook: The outdoor play area must have adequate fencing or walls a minimum of 4 feet in height. Fencing, including gates, must be continuous and must not have gaps or opening larger than 3 inches that would allow children to exit the outdoor play area. The base of the fence must remain at ground level, and be free from erosion or build-up to prevent inside and outside access by children or animals. These areas must have at least two exits, with at least one being remote from the buildings. If an outdoor play area was approved for usage by the Department prior to October 25, 2017, no new exits are required to be added to meet this standard. However, if outdoor play area fencing is changed then the standard would apply and two exits must be provided. The facilitys fencing was inadequate in that [the wooden panels are broken/missing].
Report comments
This standard was non-compliant on previous revisit inspection dated 1/8/2025. On today's follow inspection, the following still needs to be repaired; - The white fence surrounding the playground was missing the gate, at this time it is open and falling off the hinges. -Since the gate is damaged, the children have access to the basketball court area and the fence in the basketball area is in poor condition. There are broken and missing panels throughout the perimeter. In addition to the fence, the following needs repair in the playground area; - The water fountain in the playground appears to have been partly removed and is inoperable This is the second occurrence and a notic ... [truncated]
Correction status
Due by February 21, 2025
More details
Report section
PHYSICAL ENVIRONMENT - 21 - Outdoor Play Space Group: Sec. 7-37, Ordinance and DCF Handbook
Official code
21-11
View official report
Medium concern: Facility condition
Report finding
3.1(A), Handbook: All child care facilities must be clean, in good repair, free from health and safety hazards and from evidence of, or presence of, vermin infestation. An area(s) of the facility was observed to not be in good repair.
Inspector notes
The following area was found in need of repair: - two ceiling tiles observed with liquid stains and one of them is sagging down - peeling pain observed on the classroom door - strong urine order in the restroom
Correction status
Due by January 22, 2025
More details
Report section
PHYSICAL ENVIRONMENT - 10 - General Facility Requirements Group: Sec. 7-35, Ordinance and DCF Handbook
Official code
10-14
Medium concern: Equipment or readiness
Report finding
3.5(F), Handbook: The outdoor play area must have adequate fencing or walls a minimum of 4 feet in height. Fencing, including gates, must be continuous and must not have gaps or opening larger than 3 inches that would allow children to exit the outdoor play area. The base of the fence must remain at ground level, and be free from erosion or build-up to prevent inside and outside access by children or animals. These areas must have at least two exits, with at least one being remote from the buildings. If an outdoor play area was approved for usage by the Department prior to October 25, 2017, no new exits are required to be added to meet this standard. However, if outdoor play area fencing is changed then the standard would apply and two exits must be provided. The facilitys fencing was inadequate in that [the wooden panels are broken, missing].
Inspector notes
The following was observed in need of repair; - The white fence surrounding the playground is missing the gate, appears to have been removed -Since the gate is missing, the children have access to the basketball court area and the fence in the basketball area is in poor condition. There are broken and missing panels throughout the perimeter. In addition to the fence, the following needs repair in the playground area; - The black plastic playground border is torn and needs repair/replacement - The water fountain in the playground appears to have been partly removed and is inoperable
Correction status
Due by January 22, 2025
More details
Report section
PHYSICAL ENVIRONMENT - 21 - Outdoor Play Space Group: Sec. 7-37, Ordinance and DCF Handbook
Official code
21-11
View official report
Medium concern: Equipment or readiness
Report finding
Sec. 7-5.03(i), Ordinance: Play equipment such as climbing apparatus, slide, and swings shall be in good repair, placed in a safe location, and anchored firmly to prevent shifting, tilting, moving, or falling.3.12(B), Handbook: All playground equipment must be securely anchored, unless portable or stationary by design, in good repair, maintained in safe and sanitary condition, and placed to ensure safe use by the children.The [see below]was not securely anchored.
Inspector notes
The play structure was observed with chipped paint. The outside surface (turf) was observed to be lifting in several areas that need to be secured.
Correction status
Due by August 26, 2024
More details
Report section
PHYSICAL ENVIRONMENT - 24 - Outdoor Equipment Group: Sec. 7-5.03, Ordinance and DCF Handbook
Official code
24-01
View official report
Medium concern: Health or food records
Report finding
Sec. 7-4.05(b), Ordinance: Prior to the first day of being employed by a child care facility, all child care personnel, excluding temporary substitutes, shall have on file at the child care facility a signed statement from a licensed physician or authorized agent of a Florida County Health Department attesting that the employee is in good health in order to care for children.The health assessment statement shall be documented on the No. 8, Physicians Statement of Good Health for Child Care Center Personnel, and updated every two (2) years.See Supplemental Inspection Sheet for name(s) of staff without current No. 8 on file.
Report comments
There is a staff member without a valid physical. See supplement.
Correction status
Due by April 25, 2024
More details
Report section
HEALTH REQUIREMENTS - 05 - Health Requirements Group: Sec. 7-4.05, Ordinance
Official code
05-01
View official report
Medium concern: Equipment or readiness
Report finding
Sec. 7-5.03(i), Ordinance: All equipment must be installed safely and maintained in a safe condition. All play equipment shall be of substantial construction and free from rough edges, sharp corners, pinch and crush points, splinters, and exposed bolts. Ladders on slides must have a handrail. The following equipment in the outdoor space is broken and needs to be repaired: [white fence].
Report comments
The white fence leading to the basketball court is in need of repair. There were rusted nails protruding and missing rails. There was also no gate door/barrier.
Correction status
Due by December 26, 2023
More details
Report section
PHYSICAL ENVIRONMENT - 24 - Outdoor Equipment Group: Sec. 7-5.03, Ordinance and DCF Handbook
Official code
24-03

Questions to ask

Suggested questions for parents based on recorded violations in inspection reports. If there are not enough source-backed violations, you will see general questions for daycare.

Finding-specific

Could you describe your current process for ensuring fire drills are conducted and documented on a monthly basis?

Why ask this
Why ask this
Public records from an April 2026 inspection indicate that documentation for fire drills was missing for two months. This question helps clarify how the center now tracks these required safety procedures.
Context
A later clean inspection occurred on May 13, 2026.
Related violations
Finding-specific

What steps have been taken to ensure the playground fencing remains secure and in good repair for the children?

Why ask this
Why ask this
Available inspection records show multiple findings regarding the condition of the outdoor play area fencing between 2023 and 2026. Asking about current maintenance practices helps families understand how the facility manages the upkeep of its outdoor space.
Context
A later clean inspection occurred on May 13, 2026.
Related violations
Finding-specific

How do you manage the tracking of immunization records to ensure they remain current for all children in your care?

Why ask this
Why ask this
Official inspection reports from 2024 and 2025 noted instances where immunization records for children were either missing or expired. This question allows the director to explain the system currently in place to keep these health files up to date.
Related violations
Finding-specific

What is your approach to maintaining the facility's interior, such as addressing repairs for ceiling tiles or other maintenance needs?

Why ask this
Why ask this
Public records from an inspection in early 2025 noted areas of the facility that were in need of repair. This question helps parents understand the center's routine for identifying and completing facility maintenance.
Related violations
Finding-specific

How do you ensure that all staff members have their required health assessments on file before they begin working with children?

Why ask this
Why ask this
An official inspection report from 2024 identified a staff member who did not have a current health assessment on file. This question provides insight into how the center monitors personnel requirements.
Related violations